
Roller Shutters · Supply · Install · Repair
Fire-Rated Shutters in Dubai: Supply, Installation and Servicing
Fire-rated shutters in Dubai close an opening automatically when the fire alarm or heat triggers them, holding back fire and smoke for the period the product was tested to. We supply, install, drop test and repair fire shutters in Dubai and Abu Dhabi where the building's fire strategy calls for them, working from the approved product's documents and the consultant's specification.
- Open 24/7, including Fridays and holidays
- Dubai and Abu Dhabi
- No charge for the site visit
- 24/7 call-outs
- Same-day visits
- Free site visit
- Written quote first
- English and Arabic
- All major brands
What a fire-rated shutter does
A fire-rated shutter, also called a fire shutter or rolling fire door, is a steel roller shutter built and tested to resist fire for a stated time, for example 60, 120 or 240 minutes. It normally stays open during daily use and closes when the building's fire alarm sends a signal, when a heat-sensitive fusible link melts, or when power to the release is lost.
It is a life safety and property protection product, not just a security shutter. Its job is to keep a fire inside one compartment long enough for people to get out and for the fire service to act.
Fire test standards and what a rating means
A fire shutter's rating comes from a fire test on a complete sample of that product at an accredited laboratory, and from the classification and listing that follow. The rating belongs to the tested design and size range. A plain shutter cannot be made fire-rated by adding parts on site.
Common test standards seen in the UAE include EN 1634-1 for fire resistance of doors and shutters, with results classified under EN 13501-2, BS 476 Part 22 on older British-based specifications, and UL 10B on American-based specifications. Which one applies is set by the project specification and the authority, not by the installer.
| Term | What it means |
|---|---|
| E (integrity) | The shutter stops flames and hot gases passing through for the stated minutes |
| EI (integrity and insulation) | Also limits the temperature rise on the unexposed side, harder for steel shutters to achieve |
| EW (radiation) | Integrity plus a limit on heat radiated from the unexposed face |
| Duration | Tested period, for example 60, 120 or 240 minutes |
| Fusible link | Metal link that melts at a set temperature and releases the shutter |
| Fail-safe release | Shutter closes if power or the alarm signal is lost |

Fire-Rated Shutters: typical specifications
- Curtain
- Galvanised steel slats designed for fire resistance
- Rating
- As tested, commonly 60, 120 or 240 minutes
- Test standards seen
- EN 1634-1 with EN 13501-2, BS 476 Part 22, UL 10B
- Classification
- Integrity (E), sometimes EW or EI as tested
- Activation
- Fire alarm signal, fusible link, loss of power
- Descent
- Governed or motor-controlled speed
- Daily operation
- Motorised or manual open, depending on design
- Backup
- Battery backup on many systems
- Approvals
- Product and installation acceptable to the local Civil Defence authority
- Documentation
- Manufacturer test, classification and installation records
Certification, approvals and our role
In the UAE, fire safety products and their installation generally need to be acceptable to the local Civil Defence authority, and the building's fire strategy and consultant decide where a fire shutter is required and what rating it needs. We do not certify fire shutters and we do not issue fire ratings.
What we do is supply and install products that come with their manufacturer's test and approval documents, follow the installation instructions those documents rely on, and carry out drop tests, servicing and repairs with matching parts. If a shutter's paperwork is missing or a change would affect its rating, we tell you and refer the question to the consultant or manufacturer.
How fire shutters close safely
A fire shutter must close at a controlled speed so it does not injure anyone below. Most use a governor or a motor-controlled descent, with the curtain released by an electromagnetic holder, a motor brake release or a fusible link.
- Interface with the fire alarm panel to close on alarm
- Fusible link as a heat-activated backup on many designs
- Governed or controlled descent speed
- Battery backup so it can close and, on some systems, reopen after a power cut
- Audible and visual warning before closing on some designs
- Obstruction detection to pause and then continue closing on some designs

Where fire-rated shutters are used in Dubai and Abu Dhabi
Typical locations are compartment walls in warehouses in Jebel Ali, DIP and Mussafah, between a loading bay and storage, mall service corridors and kitchen counters, car park ramps between basement levels, plant rooms, conveyor openings and serveries in hotels and hospitals.
The fire consultant marks each one on the fire strategy drawings with its required rating. Our job starts from those drawings, not from a guess on site.
Where fire-rated shutters are used in Dubai and Abu Dhabi
- Warehouse compartment walls
- Loading bay and storage separations
- Mall service corridors
- Kitchen and servery counters
- Basement car park ramps
- Plant rooms and conveyor openings
We service and repair fire-rated shutters from brands such as Hormann and Novoferm, as well as most other makes found in the UAE. We are an independent service, not a dealer for these brands.
Installation requirements
The tested design dictates the fixings, guide details, wall type, clearances and how the head box is sealed. The surrounding wall must have at least the same fire resistance as the shutter, and gaps around the frame are closed with suitable fire-stopping products.
Wiring to the fire alarm panel and any fire-rated power supply is coordinated with the MEP contractor. After installation we commission the shutter, carry out a drop test with the alarm interface, and hand over the documents for the building's records.
Servicing and drop testing
A fire shutter that sits open for months can fail when it is finally needed: guides fill with dust, the governor stiffens, batteries go flat or someone parks a pallet under it. Regular servicing and drop testing, commonly every six or twelve months depending on the building's maintenance regime, catches this early.
We test closing on alarm signal and on loss of power, check closing speed, inspect the curtain, guides, fusible link and batteries, clear obstructions and record the results so the facility manager has evidence for inspections.

Repairs and upgrades
Repairs use parts that match the original tested design wherever possible. Replacing a curtain, governor or release with non-matching parts may affect the rating, so for anything beyond like-for-like repair we check with the manufacturer or consultant first. If an old shutter cannot be traced to its documents, the honest answer is often replacement with an approved product.
Signs a fire shutter may not close when needed
A fire shutter can sit open for years and look fine while a fault develops. Facility teams in Dubai and Abu Dhabi often spot these warning signs during routine walk rounds.
- Pallets, racking, trolleys or display stands sit inside the closing line.
- The guides are bent, painted over or packed with dust and debris.
- The control panel shows a fault light, or its battery warning is on.
- The shutter has been manually wound up after a test and not reset to automatic.
- Cables to the panel or the fire alarm interface have been cut or disconnected during fit-out works.
- The service label or log book shows no test in the last year.
Fire shutter uses by building type
Fire-rated shutters appear wherever the fire strategy needs to divide a large opening into separate compartments. Each setting brings its own risks.
| Building | Typical location | Common risk |
|---|---|---|
| Tower with basement car park | Between parking levels or ramps | Cars parked in the closing line |
| Shopping mall | Store fronts and service corridors | Display stock under the curtain |
| Warehouse in Jebel Ali, DIP or Mussafah | Between storage zones | Racking and forklifts hitting guides |
| Hotel or restaurant kitchen | Servery hatches | Grease build-up in guides |
| Hospital or clinic | Corridors and store areas | Beds and equipment left in the way |

After an alarm: getting the shutter back to normal
When a shutter drops on an alarm, whether real or false, it must be reset correctly. Winding it up by hand and leaving it is a common mistake that leaves the shutter unable to drop again.
- Confirm it is safeWait until the fire alarm is reset and the building is cleared for normal use.
- Check the openingLook for damage to the curtain, guides or anything trapped under the bottom rail.
- Reset the panelReset the shutter control panel or release unit following its instructions.
- Raise the shutterOpen the shutter using its normal control, not by forcing the curtain.
- Confirm it is armedCheck the panel shows normal status so the shutter will close on the next alarm.
- Record the eventNote the date, cause and any fault in the log book and report problems to your service company.
Building staff jobs and technician jobs
Fire shutters are life safety equipment, so the line between what staff can do and what a technician must do is strict.
Building staff
Keep the closing line clear and marked on the floor, report damage straight away, check the panel shows a normal status each day, and keep the log book where the technician and inspectors can find it.
Trained technician
Drop tests, governor and speed checks, spring and barrel work, panel and battery checks, alarm interface testing and any repair to the curtain or guides. Fire shutter parts should only be replaced with parts suitable for that rated system.
Questions for facility managers before buying
Buying a fire shutter is not like buying a security shutter. Ask these questions before you sign.
- What fire rating does the building's fire strategy require at this opening?
- Which test standard has the shutter system been tested to, and can you see the test evidence?
- Is the wall and fire stopping around the frame included, or done by others?
- How will the shutter link to the fire alarm, and who tests that link?
- What documents are handed over for the building's records?
- What does a planned service include and how often is it recommended?
Fire-Rated Shutters: common faults and fixes
| Symptom | Likely cause | What the technician does |
|---|---|---|
| Shutter does not close on alarm | Release not wired, faulty relay or flat battery | Tests the interface and backup, repairs the release |
| Closes too fast | Governor or brake fault | Takes it out of use and repairs or replaces the governor |
| Closes and stops halfway | Obstruction, dirty guides or damaged slats | Clears guides and replaces damaged slats |
| Will not reopen after a test | Motor, reset mechanism or control fault | Repairs the reset and checks the controls |
| Fusible link missing or painted over | Tampering or poor maintenance | Replaces the link with the correct rated part |
| Goods stored under the shutter | Housekeeping issue | Advises the site and marks the drop zone |
What affects the price of fire-rated shutters
Every site is different, so we quote after a free site visit. These are the main things that change the price.
Longer durations and EI or EW classes need heavier constructions.
Larger openings mean more curtain and stronger guides and barrel.
Alarm interface, battery backup and warning devices add to a basic release.
Wall preparation and fire-stopping around the frame add labour and materials.
Products with full approval documents cost more than unrated shutters, for good reason.
Planned drop testing visits are priced by number of shutters and frequency.
From enquiry to handover
- Call or WhatsAppTell us what the door or gate is doing. A photo or 10 second video helps the technician bring the right parts.
- Site visit, same day where possibleA technician inspects the whole system, not only the part that failed, and tests safety devices.
- Clear written quoteYou see what failed, the options and the price before any work starts. No obligation.
- Repair, test and handoverWe fix, balance and test the door or gate, show you the manual release and clean up.
Recent roller shutters jobs by our team

Manual rolling shutter converted to automatic, Al Quoz, Dubai 
Rolling shutter installation, Al Mizhar, Dubai 
Rolling shutter repair, Dubai Investments Park 
Rolling shutter installation, Ajman 
Rolling shutter motor installation, Al Nahda 
Manual rolling shutter converted to automatic, Al Quoz, Dubai
Photos from real jobs by our team across Dubai, Abu Dhabi and the northern emirates.
Related products
Motorised Roller ShuttersElectric roller shutters with tubular or external motors, remote or key switch control and a manual override for power cuts.
Manual Roller ShuttersSpring-assisted push-up and chain or gear operated shutters for shops, stores and warehouses, no power needed.
Industrial Sectional DoorsLarge insulated sectional doors for warehouses, loading docks and workshops, with vision panels and wicket doors.
High Speed DoorsFast acting fabric rapid roll doors for warehouses, cold stores, food plants and clean areas.
Insulated Roller ShuttersDouble-skin foam-filled slats that reduce heat gain, noise and dust compared with single-skin steel shutters.
Repair and maintenance
Already have fire-rated shutters? We repair and maintain existing installations too, whoever fitted them.
Fire-Rated Shutters across Dubai and Abu Dhabi
Site surveys, installation and repairs in every Dubai community and Abu Dhabi district. Popular areas:
Fire-Rated Shutters: frequently asked questions
What is a fire-rated shutter?
It is a steel roller shutter tested to resist fire for a stated time, such as 60, 120 or 240 minutes. It usually stays open and closes automatically on a fire alarm signal, heat or loss of power to hold fire and smoke in one compartment.
Which standards are fire shutters tested to?
Common ones are EN 1634-1 with classification to EN 13501-2, BS 476 Part 22 and UL 10B. The project specification and the authority decide which applies. The rating belongs to the tested product, not to the installer.
Do you certify fire shutters?
No. Fire ratings come from the manufacturer's tests and the approvals that follow. We supply and install documented products, follow their installation requirements, and carry out drop tests, servicing and repairs.
Can a normal roller shutter be upgraded to fire-rated?
No. A fire rating comes from testing a complete product design. Adding parts to a standard shutter does not create a rating. If the fire strategy requires a fire shutter, an approved fire-rated product is needed.
How often should a fire shutter be tested?
Commonly every six or twelve months, depending on the building's maintenance regime and the authority's requirements. Each visit should include a drop test, a check of the alarm interface and batteries, and a written record.
What is the difference between E and EI ratings?
E means integrity: the shutter stops flames and hot gases for the stated time. EI also limits the temperature rise on the unexposed side. Steel shutters more commonly achieve E or EW. The fire strategy states which is needed.
How does a fire shutter close if the power fails?
Most designs are fail-safe: losing power or the alarm signal releases the curtain, which descends at a controlled speed. Many have a battery backup to control the closing and sometimes to reopen after the event.
Why must nothing be stored under a fire shutter?
If pallets, racking or goods block the drop zone, the shutter cannot close and the compartment is lost. Keep the area under every fire shutter clear and marked, and check it during routine walk-rounds.
Can you repair an old fire shutter?
Yes, with matching parts where the original design can be identified. If documents are missing or a repair would affect the rating, we refer it to the manufacturer or consultant, and replacement may be the safer route.
Where are fire shutters needed?
Where the building's fire strategy shows a fire-rated opening, such as compartment walls in warehouses, mall service corridors, kitchen counters and car park ramps. The fire consultant decides, not the shutter installer.
Do you offer fire shutter maintenance contracts?
Yes. We offer planned drop testing and servicing for buildings in Dubai and Abu Dhabi, with written records for each shutter. Call 050 495 3512 with the number of shutters to arrange a site visit and quote.
Can a fire shutter also be used as a daily security shutter?
Many fire shutters open and close daily on a motor and also drop on alarm, so they serve both roles. The key point is that daily use must not interfere with the fire release. Locks or padlocks that stop the curtain dropping are not acceptable on a rated shutter.
Who is responsible for servicing a fire shutter in a rented unit?
It depends on the lease and the building's arrangement. In some malls and towers the landlord or facility manager maintains all fire shutters; in others the tenant is responsible for shutters within their unit. Check your tenancy terms and the building's fire safety records.
What records should we keep for our fire shutters?
Keep the handover documents, any test evidence supplied with the shutter, a log of every service and drop test, and notes of faults and repairs. Inspectors and insurers often ask to see these, and a clear history makes faults easier to trace.
Can a fire shutter be fitted to a kitchen serving hatch?
Yes, small fire-rated shutters are made for counters and hatches. They are common in hotel and restaurant kitchens where the fire strategy requires the opening to close. Grease is the main problem there, so guides need regular cleaning to keep the curtain free.
Why does our fire shutter not drop after it was opened by hand?
Often the shutter was wound up manually after a test or alarm and the release system was never reset, so it is not armed. It may also have a panel fault or flat battery. A technician should reset and test it before you rely on it again.
Related searches
- rolling shutter sharjah
- automatic rolling shutter
- speed doors dubai
- insulated shutter
- insulated roller shutter
- shutter repair
- rolling shutter repair
- roller shutters Dubai
- roller shutters Abu Dhabi
- motorised roller shutters Dubai
- manual roller shutters Dubai
- industrial sectional doors Dubai
- high speed doors Dubai
- insulated roller shutters Dubai
- roller shutter repair near me
- الشتر الرول
Get a quote for fire-rated shutters
Free site visit to measure and check the opening, then a written quote. Same-day visits wherever possible.